PVE/Linux安装nut管理apc BK650M2-CH ups自动关机

发布时间:December 9, 2021 // 分类: // 9 Comments

先查看usb是否识别ups:

lsusb
Bus 001 Device 054: ID 051d:0002 American Power Conversion Uninterruptible Power Supply

安装:

apt install nut-server nut-client

配置nut运行为服务器模式,可控制多台电脑。

/etc/nut/nut.conf 
MODE=netserver

设置nut和ups连接方式,修改此配置后需重新启动upsdrvctl start生效。

/etc/nut/ups.conf
[myups]
       driver = usbhid-ups
       port = auto
       desc = "APC UPS"
       #忽略低电量和低运行时间,有的断电后会马上关机
       ignorelb
       #重写ups返回的低电量和低运行时间值,可用于控制停电时关机时间,满足一个关机,-1为禁用此项
       override.battery.charge.low = 99
       override.battery.runtime.low = -1
       #可以都设置为-1禁用ups低电量自动关机,使用下面的脚本自定义关机

连接ups,nut-server启动时自动加载,usb拔出后需手工启动。

upsdrvctl start

设置nut server监听ip和端口:

/etc/nut/upsd.conf 
LISTEN 0.0.0.0 3493

设置客户端连接验证密码:

/etc/nut/upsd.users
#管理员可set更改ups内变量参数,master可设置FSD关机标签,slave收到通知后关机
[admin]
    password = 123456
    actions = SET FSD
    instcmds = ALL
    upsmon master
[user1]
    password = 123456
    actions = FSD
    #instcmds = ALL
    upsmon master
#别的电脑连接使用此用户
[user2]
    password = 123456
    #actions = SET
    #instcmds = ALL
    upsmon slave

设置upsmon客户端连接nut server监控ups状态,当断电后执行关机等操作:

/etc/nut/upsmon.conf 
MONITOR myups@localhost 1 user1 123456 master

upsmon默认监控断电且ups电量过低时执行关机,可自定义关机:

upsmon.conf 
NOTIFYCMD /sbin/upssched
#当使用电池来电时syslog并执行上面的命令
NOTIFYFLAG ONBATT SYSLOG+EXEC
NOTIFYFLAG ONLINE SYSLOG+EXEC

upssched自定义操作:

/etc/nut/upssched.conf 
CMDSCRIPT /usr/local/bin/upssched
#此目录nut要可写
PIPEFN /run/nut/upssched.pipe
LOCKFN /run/nut/upssched.lock
#断电10秒后执行上面脚本并发送power-off参数
AT ONBATT * START-TIMER power-off 10
#来电后取消上面定时
AT ONLINE * CANCEL-TIMER power-off

关机脚本,要添加可执行权限:

/usr/local/bin/upssched
#! /bin/sh

case $1 in
  power-off)
    /sbin/upsmon -c fsd
    ;;
  *)
    logger -t upssched "Unrecognized command: $1"
    ;;
esac

启动并查看ups信息:

systemctl restart nut-server.service 
systemctl restart nut-client.service 
upsc myups

配置nut-cgi web管理界面:

apt install nut-cgi --no-install-recommends fcgiwrap nginx

nut-cgi连接nut-server配置:

/etc/nut/hosts.conf
MONITOR myups@localhost 1 user1 123456 master

nginx配置文件:

server {
  listen     89;
  charset utf-8;
 
  location /{
    alias /usr/share/nut/www/;
    try_files $uri $uri/ /index.html;
  }
 
  location /cgi-bin/nut/ {
    gzip off;
    alias /usr/lib/cgi-bin/nut/;
    include /etc/nginx/fastcgi_params;
    fastcgi_param SCRIPT_FILENAME /usr/lib/$fastcgi_script_name;
    fastcgi_pass  unix:/var/run/fcgiwrap.socket;
  }
  access_log off;
}

nut web界面效果:
2021-12-10_080005.jpg

参考:
https://loganmarchione.com/2017/02/raspberry-pi-ups-monitor-with-nginx-web-monitoring/
https://srackham.wordpress.com/2013/02/27/configuring-nut-for-the-eaton-3s-ups-on-ubuntu-linux/
https://alainlam.cn/?p=56
https://untitled.pw/hardware-iot/2767.html
https://www.wangchucheng.com/zh/posts/setting-up-ups-with-nut-on-linux/
https://forums.contribs.org/index.php?topic=44443.0

标签:proxmox, pve, ups, nut

有 9 条 关于" PVE/Linux安装nut管理apc BK650M2-CH ups自动关机 "的评论

  1. ryan

    请问下nginx配置好了,怎么和这个nut链接呢?最后可视化管理这块能给个详细一点的教程么?谢谢。

    1. 海运

      写的很详细了啊,/etc/nut/hosts.conf用以nut-cgi连接nut服务器参数,nginx配置文件连接nut-cgi,注意修改nginx内linsten port。

  2. kgami

    想请教一下,设置了的电脑自动关机之后,几秒后UPS怎么也跟着关机了,导致另外一台电脑没关机就断电了,有没有办法避免UPS关机

    1. 海运

      ups不知有没选项可设置此参数,不过你可以在另外一台电脑上安装nut客户端自动关机。

  3. 杰迪武士

    此文甚好甚强巨,依照此文在树莓派2 + Rasbian上部署成功
    感谢博主美文共赏

  4. 海风

    override.battery.charge.low以及override.battery.runtime.low的作用是自动关闭UPS还是服务器呢。

    1. 海运

      关闭服务器

  5. 孤狼

    擦。。。。apcupsd会失联 nut在冲到到100的时候会ONBATT进入关机状态,我想想办法解决下

    1. 孤狼

      ups_status_set: seems that UPS [BK650M2-CH] is in OL+DISCHRG state now. Is it calibrating or do you perhaps want to set 'onlinedischarge' option? Some UPS models (e.g. CyberPower UT series) emit OL+DISCHRG when offline.

发表评论

分类
最新文章
最近回复
  • Jimmy: 方法一 nghtp3步骤需要改成如下才能编译成功: git clone https://git...
  • 海运: 地址格式和udpxy一样,udpxy和msd_lite能用这个就能用。
  • 1: 怎么用 编译后的程序在家里路由器内任意一台设备上运行就可以吗?比如笔记本电脑 m参数是笔记本的...
  • 孤狼: ups_status_set: seems that UPS [BK650M2-CH] is ...
  • 孤狼: 擦。。。。apcupsd会失联 nut在冲到到100的时候会ONBATT进入关机状态,我想想办...
  • 海运: 网络,找到相应的url编辑重发请求,firefox有此功能,其它未知。
  • knetxp: 用浏览器F12网络拦截或监听后编辑重发请求,修改url中的set为set_super,将POS...
  • Albert: 啊啊啊啊啊啊啊啊啊 我太激动了,终于好了英文区搜索了半天,翻遍了 pve 论坛没找到好方法,博...
  • jiangker: good, very helpful to me
  • fengfeng: N1 armbian 能有编译下内核吗。。我要开启can 不懂怎么操作